CHILLER YORK 0966.073.073

Tìm kiếm
Trang chủ Hỗ trợ kỹ thuật Bảng mã lỗi YORK CENTRIFUGAL LIQUID CHILLERS

Bảng mã lỗi YORK CENTRIFUGAL LIQUID CHILLERS

Bảng mã lỗi YORK CENTRIFUGAL LIQUID CHILLERS

 

SECTION 6 TROUBLE SHOOTING

TABLE 1 - CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL CENTER DISPLAY

SHUTDOWN CAUSE CONTROL CENTER DISPLAY

GOVERNING CONTROL FUNCTION

DAY OF WEEK

TIME OF DAY

CAUSEOF SHUTDOWN

METHODOF RESTART

DESCRIPTION

OPERATING POINT

ON RISE

ON FALL

MON.

10:00 AM

Low Water

Temperature

Autostart

Low Water (LWT)

Chilled water setpoint

4°F below chilled water setpoint

MON.

10:00 AM

Low Water Temperature VSD

Autostart

Low Water (LWT)

Chilled water setpoint

4°F below chilled water setpoint

MON.

10:00 AM

Flow Switch

Autostart

Flow Switch

 

 

MON.

10:00 AM

System Cycling

Autostart

A remote command (computer relay contact or manual switch)

 

 

MON.

10:00 AM

Multi-Unit Cycling

Autostart

(Optional)

Lead-Lag Sequence Control

 

 

MON.

10:00 AM

Internal Clock

Autostart

Internal Clock

 

 

MON.

10:00 AM

AC Undervoltage

Autostart

<15% FLA for 25

continuous seconds

 

 

MON.

10:00 AM

Power Fault

Autostart

CM-2 Current Module or Solid State Starter

 

 

 

 

Remote Stop

 

Energy Management System

 

 

MON.

 

Anti-Recycle, 20 Min. Left

 

Anti-Recycle Timer

 

 

MON.

10:00 AM

Low Evap. Pressure

 

Low Evap. Pressure Transducer (LEP)

5.43 PSIA

5.42 PSIA

MON.

10:00 AM

Low Evap. Pressure Brine

 

LEP external control (Brine units only)

Set to Job Spec.

Set to Job Spec.

MON.

10:00 AM

Low Oil Pressure

 

Low Oil Press. Transducer (OP) High Oil Press. Transducer (OP)

20 PSID

15 PSID

MON.

10:00 AM

High Pressure

 

High Pressure Safety Control (HP)

15 PSIG

9 PSIG

MON.

10:00 AM

Evap. Transducer or Probe Error

 

Evap. Pressure Transducer or Leaving Chilled Water Thermistor (RS1)

 

 

MON.

10:00 AM

Motor Controller - Ext. Reset

 

CM-2 or Solid State Starter or Variable Speed Drive

 

 

MON.

10:00 AM

High Discharge Temperature

 

Discharge Temperature Thermistor (RT2)

220°F

219°F

MON.

10:00 AM

High Oil Temperature

 

Oil Temperature Thermistor (RT3)

180°F

179°F

MON.

10:00 AM

Power Failure

Autostart

Micro Board undervoltage circuit on 5V unregulated supply

8.29 VDC

7.84 VDC

MON.

10:00 AM

Power Failure

 

Micro Board undervoltage circuit on 5V unregulated supply

8.29 VDC

7.84 VDC

 

 

 

 

 

 

TABLE 1 - CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL CENTER DISPLAY - CONTINUED

 

PROGRAMMED SETPOINTS

BY OPERATOR

 

START-UP OF SYSTEM AFTER SHUTDOWN

 

PROBABLE CAUSE AND SERVICE REQUIRED

4°F below chilled water setpoint (If set to 40°F would be 36°F.) (36°F minimum)

Automatic Restart when water reaches setpoint. If system is running and setpoint is increased 4°F, system will continue to run, as LWT cutout shifts to a fixed 36°F for 10 minutes.

System load is less than minimum capacity.

4°F below chilled water setpoint (If set to 40°F would be 36°F.) (36°F minimum)

If system is running and setpoint is increased

4°, VSD will Initiate Shutdown. Automatic Restart when water temperature reaches setpoint.

System load is less than minimum capacity.

 

Automatic Restart when water flow is restored to close flow switch.

Lack of water flow.

Check operation of chilled water pump.

 

Automatic Restart upon remote command.

Contact - connected to the Remote/Local cycling input of the Digital Input Board.

 

Automatic Restart upon remote command.

Contact - connected to the Multi-Unit cycling input of the Digital Input Board.

Daily Schedule programmed to shut down unit.

Will automatically restart when programmed schedule permits.

Pressing Compressor Start Switch overrides the program.

 

 

Cycling shutdown occurs when motor current is >15% FLA for 25 seconds during chiller operation.

 

Will start automatically following coastdown.

Motor Controller contacts opening and closing in less than 3 seconds due to a power fault condition.

 

Start up by start signal from remote start switch.

Remote Stop Contact Closure.

Will not start until 30 minute timer is timed out.

Will restart when time left = 00 minutes.

Minimum time between successive compressor starts is 30 minutes.

 

To restart, press compressor switch from STOP/RESET to START position.

See OPERATING ANALYSIS, Table  2

Sympton 2.

 

To restart, press compressor switch from STOP/RESET to START position.

See OPERATING ANALYSIS, Table  2

Sympton 2.

 

Will restart when pressure increases to 20 PSID.

To restart, press compressor switch from STOP/RESET to START position.

See OPERATING ANALYSIS, Table 2 Symptom 4, 5, 6, 7, 9, 10, 11.

 

Will restart when pressure falls to 9 PSIG.

To restart, press compressor switch from STOP/RESET to START position.

See OPERATING ANALYSIS, Table  2

Symptom 1 - High Discharge Pressure.

 

To restart, press compressor switch from STOP/RESET to START position.

Defective Evap. Pressure Transducer or Leaving Chiller Water thermistor (RS1). LCWT minus saturation temp. is less than -2.5°F or greater than 25°F. Checked

every 10 minutes following a 10-min. bypass at start-up.

 

Reset the device that caused the shutdown. Chiller will start automatically.

CM-2 or Solid State Starter or Variable Speed Drive has shut down chiller.

 

To restart, press compressor switch from STOP/RESET to START position.

Condenser tubes dirty or scaled or high condenser water temperature. See Symptom 1, Table 2.

 

To restart, press compressor switch from STOP/RESET to START position.

Dirty oil filter or restricted oil cooler line. Change oil filter. See Sympton 9, Table 2.

Optional AUTO Restart Plug is installed on Micro Board.

Will restart automatically when voltage reaches 8.29VDC. An undervoltage circuit on Micro Board monitors the 5VDC unregulated supply for an undervoltage condition.

Power Failure.

Auto restart plug is removed on Micro Board.

To restart, press compressor switch to STOP/RESET position and then to START position.

Power Failure.

 

 

 

TABLE 1 - CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL CENTER DISPLAY - CONTINUED

SHUTDOWN CAUsE CONTROL CENTER DISPLAY

GOVERNING CONTROL FUNCTION

DAY OF WEEK

TIME OF DAY

CAUSEOF SHUTDOWN

METHODOF RESTART

DESCRIPTION

OPERATING POINT

ON RISE

ON FALL

MON.

10:00 AM

Oil Pressure

Transducer Error

 

High Oil Pressure Transducer or Low

Oil Pressure Transducer

60 PSID

59 PSID

 

 

Vane Motor Switch Open

Autostart

Vane Motor Switch

 

 

MON.

10:00 AM

Starter Malfunction Detected

 

Motor Current >15% for 10 seconds with Control Center not calling for motor to run.

 

 

MON.

10:00 AM

Program Initiated Reset

Autostart

Micro Board

 

 

 

 

Replace RTC-IC Chip Reprogram Setpoints

 

RTC-IC Chip

 

 

MON.

10:00 AM

Low Oil Temperature

Autostart

Oil Temperature Thermistor (RT3)

71.0°F

55°F

MON.

10:00 AM

Faulty Discharge Temperature Sensor

 

Discharge Temp. Thermistor (RT2) disconnected or faulty (min. system operating temp. = 32°F)

30.0°F

29.9°F

MON.

10:00 AM

Low Line Voltage (SSS units only)

 

SSS Logic Board

See legend on wiring diagram.

MON.

10:00 AM

Motor Phase Current Unbalance (SSS units only)

 

SSS Logic Board

See Section 2.

 

 

 

 

 

 

TABLE 1 - CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL CENTER DISPLAY - CONTINUED

 

PROGRAMMED SETPOINTS

BY OPERATOR

 

START-UP OF SYSTEM AFTER SHUTDOWN

 

PROBABLE CAUSE AND SERVICE REQUIRED

 

Will start at 59 PSID when compressor switch is placed to STOP/RESET and then START.

This Shutdown is provided to check on Oil pressure Transducers for failure in the high state.Replace Oil PressureTransducer in oil sump or compressor.

 

Restart automatically after Vane Motor arm linkage is set properly. Press STOP/RESET and then START switch.

Vanes are set improperly. Reset vane linkage, check vane positions using the Service key switch and proper keys on the MicroComputer Control Center or switch of capacity board of Variable Speed Drive.

 

Press compressor STOP/RESET switch and then START switch.

Check motor starter operation. Motor current value greater than 15%.

 

 

Watchdog timer circuit has reset software program. Chiller will automatically restart.

 

Reprogram the Control Center Setpoints and proceed with Normal Start-up.

Weak Battery.

Replace RTC-IC chip U16.

 

Press STOP/RESET switch and then START switch.

Oil Temperature Thermistor disconnected from Analog Input Board. Reconnect or replace open sensor.

 

Press STOP/START switch and then START switch.

Faulty Discharge Temperature Thermistor (RT2) or disconnected from Analog Input Board. Connect or replace open sensor.

 

Chiller will automatically restart when all phases of line voltage increase to the minimum required starting level.

Low AC Line Voltage

 

Press STOP/RESET switch and then START switch.

Motor Phase Current Unbalance

 

TABLE 2 - OPERATING ANALYSIS CHART

 

RESULTS

 

POSSIBLE CAUSE

 

REMEDY

 

1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURE

 

Temperature difference between liquid refrigerant out and water off condenser higher than normal.

Air in condenser.

Purge unit operates automatically to take care of this condition. Test for air leaks if display

reads:  WARNING – EXCESS PURGE

High discharge pressure.

Condenser tubes dirty or scaled.

Clean condenser tubes. Check water conditioning.

 

High condenser water temperature.

Reduce condenser water inlet temperature. (Check cooling tower and water circulation.)

Temperature difference between condenser water on and water off higher than normal, with normal cooler pressure.

Insufficient condensing water flow.

Increase the quantity of water through the condenser to proper value.

 

2. SYMPTOM: ABNOrMALLY LOW SUCTION PRESSURE

 

Temperature difference between leaving chilled water and refrigerant in cooler greater than normal with high discharge temperature.

Insufficient charge of refrigerant.

Check for leaks and charge refrigerant into system.

Flow orifice blocked.

Remove obstruction.

Temperature difference between leaving chilled water and refrigerant in the cooler greater than normal with normal discharge temperature.

Cooler tubes dirty or restricted.

Clean cooler tubes.

Temperature of chilled water too low with low motor amperes.

Insufficient load for system capacity.

Check prerotation vane motor operation and setting of low water temperature cutout.

 

3. SYMPTOM: HIGH COOLER PRESSURE

 

High chilled water temperature.

Prerotation vanes fail to open.

Check the prerotation vane motor positioning circuit.

 

System overloaded.

Be sure the vanes are wide open (without overloading the motor) until the load decreases.

 

4. SYMPTOM: NO OIL PRESSURE WHEN SYSTEM START BUTTON PUSHED

 

Low oil pressure displayed on control center; compressor will not start.

Oil pump running in wrong direction.

Check rotation of oil pump. (Electrical Connections)

 

Oil pump not running.

Check electrical connecrtions to oil pump and press manual reset on oil pump starter (on condenser shell in front of purge unit).

 

5. SYMPTOM: COMPRESSOR STARTS, NORMAL OIL PRESSURE DEVELOPS, FLUCTUATES FOR SHORT WHILE, THEN COMPRESSOR STOPS ON OIL PRESSURE CUTOUT

Oil pressure normal, fluctuates, then com- pressor stops on Oil Pressure Cutout.

Unusual starting conditions exist, i.e., oil foaming in reservoir and piping due to lowered system pressure.

Drain the oil from the compressor and charge new oil into the compressor. (See “Oil Charging Procedure”, page 44.)

Display reading:

LOW OIL PRESSURE

 

 

 

Burned out oil heater.

Replace oil heater.

 

 

 

TABLE 2 - OPERATING ANALYSIS CHART - CONTINUED

 

RESULTS

 

POSSIBLE CAUSE

 

REMEDY

 

6. SYMPTOM: UNUSUALLY HIGH OIL PRESSURE DEVELOPSWHEN OIL PUMP RUNS

 

Unusually high oil pressure is displayed when the oil pressure display key is pressed when the oil pump is running.

High oil pressure. Transducer defective. Relief valve is misadjsuted.

Replace low or high oil pressure transducer. Adjust external relief valve.

 

7. SYMPTOM: OIL PUMP VIBRATES OR IS NOISY

 

Oil pump vibrates or is extremely noisy with some oil pressure when pressing “Oil Pressure” display key.

Misalignment of pump or piping. Mounting bolts loose.

Bent shaft.

Worn pump parts.

Correct condition or replace faulty part.

NOTE: When oil pump is run without an oil supply it will vibrate and become extremely noisy.

Oil not reaching pump suction inlet in sufficient quantity.

Check oil supply and oil piping.

 

8. SYMPTOM: OIL PRESSURE GRADUALLY DECREASES (NOTED BY OBSERVATION OF DAILY LOG SHEETS)

 

Oil pressure (noted when pressing “Oil Pressure” display key) drops to 70% of oil pressure when compressor was originally started.

Oil filter is dirty.

Change oil filter.

Extreme bearing wear.

Inspect compressor.

 

9. SYMPTOM: OIL RETURN SYSTEM CEASESTO RETURN AN OIL/REFRIGERANT SAMPLE

 

Oil refrigerant return not functioning.

Filter-drier in oil return system dirty.

Replace oil filter-drier with new.

Jet or office of oil return jet clogged.

Remove jet, inspect for dirt.

Remove dirt using solvent and replace.

 

10. SYMPTOM: OIL PUMP FAILS TO DELIVER OIL PRESSURE

 

No oil pressure registers when pressing “Oil Pressure” display key when oil pump runs.

Faulty oil pressure transducer. Faulty writing/connectors.

Replace oil pressure transducer.

 

11. SYMPTOM: REDUCED OIL PUMP CAPACITY

 

Oil pump pumping capacity low.

Excessive end clearance in pump. Other worn pump parts.

Inspect and replace worn parts.

Partially blocked oil supply inlet.

Check oil inlet for blockage.

 

12. SYMPTOM: IMPROPER PURGE UNIT OPERATION

 

Purge unit not purging and air is present in the unit.

  1. Faulty float switch assembly.
  2. Faulty three-way oil solenoid valve.
    1. Faulty exhaust solenoid valve.
      1. Faulty pressure transducer.

Check these components and replace where necessary.

Purge unit purging air and refrigerant

  1. Faulty exhaust solenoid valve.
    1. Faulty pressure transducer.
    2. Lack of cooling.

Restore refrigerant liquid cooling supply.

 

Bài viết khác

Facebook Chat
zalo